15kV Three Conductor 133% Insulation Level

15kV Three Conductor 133% Insulation Level

Armored Cable 15kV Three Conductor 133% Insulation Level

15kV Three Conductor 133% Insulation Level

7TPU-0103, 7TPU-1013, 7TPU-2023, 7TPU-3033, 7TPU-4043, 7TPU-2503, 7TPU-3503, 7TPU-5003, 7TPU-7503, 7TPU-10003

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Armored Cable 15kV Three Conductor 133% Insulation Level

El acero galvanizado o aluminio armadura entrelazada
blindado
aislamiento XLP
Las fundas de PVC interior y exterior
PRESUPUESTO
1. CONDUCTOR: Clase B Trenzado, desnudo de cobre, suave
2. conductor de la pantalla: Los cables tienen un blindaje semiconductora sobre el conductor
3. Aislamiento: Polietileno reticulado (XLP) 215 milésimas de pulgada de espesor de aislamiento
4. IDENTIFICACIÓN: Los conductores aislados se identifican por medio de una cinta adhesiva de color (negro, rojo y azul) colocados longitudinalmente bajo el blindaje metálico de cinta de cobre
5. conductor a tierra: Un conductor de tierra trenzado Clase B sin aislamiento está incluido en el conjunto de cables
6. MONTAJE: cables conductores múltiples están montados con cargas adecuadas y cinta con aglutinante
7. chaqueta interior: cloruro de polivinilo (PVC) al calor, a las llamas y una chaqueta resistente a la humedad, una clasificación de -40 ° C
8. Armadura: aluminio o acero galvanizado armadura de enclavamiento
9. Cubierta exterior: Policloruro de vinilo (PVC) al calor, a las llamas y una chaqueta resistente a la humedad, nominal -40 ° C, el color estándar es negro, pero las chaquetas de colores están disponibles bajo petición. Cumple
Ontario Hydro Espec. L-891 SM-77 prueba de la llama y el ensayo de llama vertical de la bandeja FT4
10.AMPACITY: Consultar la IEEE 835-1994 tablas para los valores de ampacidad, y el Código Eléctrico de Canadá factores de corrección
11.STANDARDS: El cable está certificado para CSA C22.2 No. 131 y No. 174 para su uso en CSA Clase 1, División 1 peligrosos (CSA HL clasificación) y CSA C68.3 y pasa el
ensayo de llama vertical de la bandeja FT4
12.TEMPERATURE: -40 ° C a 90 ° C
13.VOLTAGE: 15 kV
APLICACIONES
Para expuesta u oculta el cableado en lugares húmedos o secos. Para su uso en ventilado de transporte por cable flexible, no ventilado y canales de cable tipo escalera y ventilado en húmedo o en seco
ubicaciones. Para el entierro directo.

Después de su uso el número de pieza; «SJ» de acero «AJ» para el aluminio, (por ejemplo 7TPU-3033AJ).
Diámetros y pesos pueden variar entre los fabricantes.

Armored Cable 15kV Three Conductor 133% Insulation Level

Galvanized steel or interlocked aluminum armor
Shielded
XLP insulation
Inner and outer PVC jackets
SPECIFICATIONS
1. CONDUCTOR: Class B stranded, bare, soft copper
2. CONDUCTOR SHIELD: Cables have a semiconducting shield over the conductor
3. INSULATION: Cross-Linked Polyethylene (XLP) 215 mils insulation thickness
4. IDENTIFICATION: The insulated conductors are identified by means of a colored tape (black, red and blue) placed longitudinally under the copper tape metallic shield
5. GROUNDING CONDUCTOR: An uninsulated Class B stranded grounding conductor is included in the cable assembly
6. ASSEMBLY: Multiple conductor cables are assembled with suitable fillers and binder tape
7. INNER JACKET: Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C
8. ARMOR: Aluminum or galvanized steel interlocking armor
9. OUTER JACKET: Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C, the standard color is black but colored jackets are available on request. Meets
Ontario Hydro Spec. L-891 SM-77 flame test and FT4 vertical tray flame test
10.AMPACITY: Refer to IEEE 835-1994 tables for ampacity values, and the Canadian Electrical Code for correction factors
11.STANDARDS: The cable is certified to CSA C22.2 No. 131 and No. 174 for use in CSA Class 1, Division 1 hazardous locations (CSA HL rated) and CSA C68.3 and passes the
FT4 vertical tray flame test
12.TEMPERATURE: -40°C to 90°C
13.VOLTAGE: 15 kV
APPLICATIONS
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry
locations. For direct earth burial.

After part number use; «SJ» for steel, «AJ» for aluminum, (e.g. 7TPU-3033AJ).
Diameters and weights may vary among manufacturers.

7TPU-0103, 7TPU-1013, 7TPU-2023, 7TPU-3033, 7TPU-4043, 7TPU-2503, 7TPU-3503, 7TPU-5003, 7TPU-7503, 7TPU-10003

Armored Cable 15kV Three Conductor 133% Insulation Level en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS, Mexico

Etiquetado con: , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable