Shielded Substation Control Cable
Utility Cable Shielded Substation Control Cable
Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx
Utility Cable Shielded Substation Control Cable
aislamiento XLP
chaqueta de CPE
90 ° C, 600 V
PRESUPUESTO
1. CONDUCTORES: Clase B de cobre trenzado según la norma ASTM B-3 y B-8
2. Aislamiento: Polietileno reticulado (XLP)
3. CÓDIGO DE COLORES: ICEA Método 1, Tabla E-1 (antes de K-1) de 14-10 AWG, ICEA Método 4 (números impresos) para 8 AWG
4. Montaje: Los conductores están cableados con cargas cuando sea necesario para hacer que ronda
5. Blindaje:. 0.005 en (5 milésimas de pulgada) aplica longitudinalmente cinta de cobre corrugado
6. CHAQUETA EN GENERAL: La luz del sol polietileno clorado resistente (CPE)
7. NORMAS: Cable enumerado Tipo TC por UL 1277 requisitos. Los conductores enumeran Tipo XHHW-2 por UL 44 con VW-1 nota y conoce a S-73-532 requisitos de ICEA (NEMA WC57).
Cable en la lista para el entierro directo y cumple con la norma IEEE 1202, UL 1685 (70.000 Btu / hr), y ICEA T-29-520 (210.000 BTU / h) Pruebas Vertical Bandeja de llama
8. AMPACIDAD: Basado en no más de tres conductores en la pista de rodadura cable o tierra con una temperatura ambiente de 30ºC por 2008 Cuadro NEC 310.16, todos los valores multiconductores
han sido reducida por 2008 Tabla NEC 310.15 (B) (2) (a).
9. Temperatura: 90 ° C húmedo / seco
10.VOLTAGE: 600 V
APLICACIONES
Diseñado por el poder y el control, telemetery, control de relé, el control del tráfico, la distribución, la iluminación y la transmisión de la señal en aplicaciones de subestaciones.
Puede utilizarse en Clase 1, Div. 2 de áreas peligrosas por 2008 NEC Art. 501.
Estos cables también se ajustan a 2008 NEC artículo 336 de alimentación y la bandeja de cable de control (Tipo TC).
Utility Cable Shielded Substation Control Cable
XLP insulation
CPE jacket
90°C, 600 V
SPECIFICATIONS
1. CONDUCTORS: Class B stranded copper per ASTM B-3 and B-8
2. INSULATION: Cross-Linked Polyethylene (XLP)
3. COLOR CODE: ICEA Method 1, Table E-1 (formerly K-1) for 14-10 AWG, ICEA Method 4 (printed numbers) for 8 AWG
4. ASSEMBLY: Conductors are cabled with fillers where necessary to make round
5. SHIELDING: 0.005 in. (5-mil) longituidinally applied corrugated copper tape
6. OVERALL JACKET: Sunlight-resistant Chlorinated Polyethylene (CPE)
7. STANDARDS: Cable listed Type TC per UL 1277 requirements. Conductors listed Type XHHW-2 per UL 44 with VW-1 rating and meet ICEA S-73-532 (NEMA WC57) requirements.
Cable listed for direct burial and meets the IEEE 1202, UL 1685 (70,000 Btu/hr), and ICEA T-29-520 (210,000 Btu/hr) Vertical Tray Flame Tests
8. AMPACITY: Based on not more than three conductors in raceway or cable or earth with an ambient temperature of 30ºC per 2008 NEC Table 310.16, all multiconductor values
have been derated per 2008 NEC Table 310.15(B)(2)(a).
9. TEMPERATURE: 90ºC wet/dry
10.VOLTAGE: 600 V
APPLICATIONS
Designed for power and control, telemetery, relay control, traffic control, switching, lighting and signal transmission in substation applications.
May be used in Class 1, Div. 2 Hazardous Locations per 2008 NEC Art. 501.
These cables also conform to 2008 NEC Article 336 Power and Control Tray Cable (Type TC).
2XR-1412LCS-1, 2XR-1407LCS-1, 2XR-1405LCS-1, 2XR-1404LCS-1, 2XR-1403LCS-1, 2XR-1402LCS-1, 2XR-1212LCS-1, 2XR-1207LCS-1, 2XR-1205LCS-1, 2XR-1204LCS-1, 2XR-1203LCS-1, 2XR-1202LCS-1, 2XR-1012LCS-1, 2XR-1007LCS-1, 2XR-1005LCS-1, 2XR-1004LCS-1, 2XR-1003LCS-1, 2XR-1002LCS-1, 2XR-0804LCS-WG-1, 2XR-0803LCS-WG-1
Shielded Substation Control Cable en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS
Deja una respuesta