XLP PVC

XLP PVC

Control Cable XLP PVC

XLP PVC

1402, 1403, 1404, 1405, 1407, 1409, 1412, 1415, 1419, 1425, 1430, 1437, 1202, 1203, 1204, 1205, 1207, 1209, 1212, 1215, 1219, 1225, 1237, 1002, 1003, 1004, 1005, 1007, 1009

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Control Cable XLP PVC

aislamiento XLP
El forro de PVC
90 ° C, 600 V
PRESUPUESTO
1. CONDUCTORES: Clase B Trenzado de cobre desnudo según la norma ASTM B-3 y B-8
2. Aislamiento: Polietileno (XLPE) por ICEA S-73-532 (NEMA WC57) reticulado, cumple con UL 44 requisitos para VW-1, tipo XHHW-2 conductores
3. CÓDIGO DE COLORES: ICEA Método 1, Tabla E-2 (anteriormente K-2)
4. Montaje: Los conductores están cableados con cargas cuando sea necesario para hacer todo el año, dos cables conductores son planas
5. CHAQUETA EN GENERAL: La luz solar resistente al cloruro de polivinilo (PVC) por UL 1277
6. NORMAS: cumple con UL 1277 por los requisitos para cables TC tipo que tiene XHHW-2 conductores, cables se enumeran para el entierro directo y cumplen con la norma IEEE 1202, IEEE 383 y UL 1685.
70.000 BTU / hr pruebas de llama, así como la ICEA T-29-520, 210.000 BTU / hr ensayos a la llama
7. AMPACIDAD: Basado en no más de tres conductores en la pista de rodadura cable o tierra con una temperatura ambiente de 30ºC y una temperatura del conductor de 90 ° C por la Tabla NEC
310.16, los valores han sido reducida en su caso
8. Temperatura: 90 ° C
9. VOLTAJE: 600 V
APLICACIONES
Diseñado por el poder y el control, telemetría, control de relé, el control del tráfico, la distribución, la iluminación y la transmisión de la señal. Puede utilizarse en Clase I, Div. 2 y Clase II, Div. 2
Lugares peligrosos por NEC Art. 501 y 502. Estos cables también cumplen con el art. 392 «Bandejas de cable» y el art. 336 «El poder y la bandeja de cable de control.»

Control Cable XLP PVC

XLP insulation
PVC jacket
90°C, 600 V
SPECIFICATIONS
1. CONDUCTORS: Class B stranded bare copper per ASTM B-3 and B-8
2. INSULATION: Cross-Linked Polyethylene (XLPE) per ICEA S-73-532 (NEMA WC57), meets UL 44 requirements for VW-1, Type XHHW-2 conductors
3. COLOR CODE: ICEA Method 1, Table E-2 (formerly K-2)
4. ASSEMBLY: Conductors are cabled with fillers where necessary to make round, two conductor cables are flat
5. OVERALL JACKET: Sunlight-resistant Polyvinyl Chloride (PVC) per UL 1277
6. STANDARDS: Meets per UL 1277 requirements for Type TC cables having XHHW-2 conductors, cables are listed for direct burial and meet the IEEE 1202, IEEE 383 and UL 1685.
70,000 Btu/hr flame tests as well as the ICEA T-29-520, 210,000 Btu/hr flame tests
7. AMPACITY: Based on not more than three conductors in raceway or cable or earth with an ambient temperature of 30ºC and a conductor temperature of 90ºC per NEC Table
310.16, the values have been derated where applicable
8. TEMPERATURE: 90ºC
9. VOLTAGE: 600 V
APPLICATIONS
Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II, Div. 2
Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 «Cable Trays» and Art. 336 «Power and Control Tray Cable.»

2AX-1402, 2AX-1403, 2AX-1404, 2AX-1405, 2AX-1407, 2AX-1409, 2AX-1412, 2AX-1415, 2AX-1419, 2AX-1425, 2AX-1430, 2AX-1437, 2AX-1202, 2AX-1203, 2AX-1204, 2AX-1205, 2AX-1207, 2AX-1209, 2AX-1212, 2AX-1215, 2AX-1219, 2AX-1225, 2AX-1237, 2AX-1002, 2AX-1003, 2AX-1004, 2AX-1005, 2AX-1007, 2AX-1009

XLP PVC en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS

Etiquetado con: , , , , , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable

Deja una respuesta

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

*

Descarga Aquí este Catálogo
Comentarios recientes
Subscribase a este sitio